close

SCT-0750 Current Transformer

Current Transformer, 0.333 Voltage Output

0.75" Opening with Rating Up to 200 Amps

aac-to-vac

One moment…we are redirecting you to our partner, Aim Dynamics. https://www.aimdynamics.com/

Magnelab Aimdynamics

Back to Magnelab

Buy Now
Via Distribution
Energy Management
We offer the best of both worlds

Quick turn-around of smaller quantities, as well as larger volume competitive pricing. Our offshore advantages include the lowest labor costs in the Western hemisphere, making our pricing competitive with suppliers anywhere!

An ISO 9001:2015 certified company

Features:

  • Rated input up to 200 Amp
  • Output of 0.333 Volt at rated current Linearity accuracy ± 1%
  • Accuracy at 10% to 130% of rated current
  • Phase angle < 2 degrees (valid for 70A or higher)
  • Operates from 30 Hz to 1,000 Hz
  • 8 ft. twisted-pair lead
  • Maximum Voltage: 600 V (on bare conductor)
  • UL recognized, CE, and RoHS compliant
Description:

The SCT-0750 split core current transformer is made by current sensor manufacturer Magnelab. In fact, it transforms the AC input current of up to 200 Amps into an output voltage of 0.333 volt. These transformers are particularly suitable when installed on wiring that is already in place, as it can easily snap around the existing conductor. In addition, the SCT-0750 comes with a self-locking mechanism. These AC current sensors have a 0.75 inch opening. General usage includes recording, data logging, energy management, power monitoring and cost allocation.

Features

The SCT-0750 features a rated input of up to 200 Amps. Its output at rated current is 0.333 volt. Linear accuracy on this current sensor is impressive at 1% either way, making its actual performance very close to estimated values. The phase angle is less than 2 degrees, applicable for 70 Amps input or higher. The operating frequency range is 30 Hz to 1,000 Hz.

Options

If you need to measure or sense a larger current consider the SCT-2000 split core current transformer, which can accommodate up to 1500 amperes. Both current sensors comes with a twisted pair 22 AWG lead measuring 8 feet in length. Its maximum voltage on a bare conductor is 600 volts. It is also UL recognized, as well as being compliant with both CE and RoHS standards. Quality is guaranteed by the 10 year warranty.

Uses

Magnelab’s SCT-0750 Series split-core current sensors “sense” AC current up to 200 Amps passing through the center conductor. Split-core transformers are ideal for installation on existing electrical wiring by snapping around the conductor. The SCT series have a self-locking mechanism. Finally, custom outputs and other parameters available at customer request.

Specifications

PART NUMBER AND RATING
SCT-0750-000 No Burden Resistor*
SCT-0750-005 5 AMP
SCT-0750-010 10 AMP
SCT-0750-020 20 AMP
SCT-0750-030 30 AMP
SCT-0750-050 50 AMP
SCT-0750-070 70 AMP
SCT-0750-100 100 AMP
SCT-0750-150 150 AMP
SCT-0750-200 200 AMP
*Zener diode limits the output voltage to 22V

All Dimensions in Inches
A 2.00
B 2.10
C 0.61
D 0.75
E 0.75

AC-Split-Core-Current-Sensor-SCT-0750_chart_dimensions